HomeMy WebLinkAbout~Master - Building Board of Appeals Minutes 09/09/2013Page | 1
MINUTES OF THE REGULAR MEETING OF THE BUILDING BOARD OF APPEALS
AMES, IOWA SEPTEMBER 9, 2013
1. The regular meeting of the Building Board of Appeals was called to order by Chairman Larry
Cormicle at 4:00 p.m., September 9, 2013, in Room 235 in City Hall, 515 Clark Avenue. Present
from the Building Board of Appeals were Larry Cormicle, Dan Nutini, Brad Heemstra, Nathan
Werstein, and Larry Brandt. Chuck Haselhoff was absent. David Francis has resigned from the
Board.
Staff members present were Shawn Bayouth, Rich Higgins, Seana Perkins, Tom Henriksen,
Bruce Kinkade, Scott Ripperger, Craig Hageman, Adam Ostert, Nick Patterson, Mike Makelbust,
Judy Parks, Jessica Spoden, and Mark Lambert.
Moved by Brandt, seconded by Werstein, to approve the minutes of September 10, 2012
Vote on Motion: 5-0
Motion passed unanimously
2. Old Business
Vacation of demolition order for 2915 Oakland Street. City staff report states the house has
been repaired and is now up to code. Order of demolition needs to be rescinded from the Story
County Recorder’s office.
Moved by Brandt, seconded by Heemstra, to rescind the demolition order
Vote on Motion: 5-0
Motion passed unanimously
3. New Business
A. Motion to approve time extensions for compliance with Ames Municipal Code Chapter 8,
Division III, Sprinkler System Retrofit, Section 8.301(5). Larry Brandt asked if there were any
objections to the submittals. Larry Cormicle stated that he had read all of the requests, and
they all met the required five criteria. He also noted that the extensions would be until October
1, 2016, and that there would be no additional extensions in the future.
Moved by Brandt, seconded by Nutini, to approve the extensions
Vote on Motion: 5-0
Motion passed unanimously
B. Amendments to the Ames Municipal Code Chapter 5, Building, Electrical, Mechanical and
Plumbing Code
i. International Building Code (IBC) - Summary of significant changes by Scott Ripperger.
Page | 2
Ripperger stated that the majority of changes are mainly for clarification and slight
tweaking, i.e., all the definitions are in Chapter 2 instead of spreading them out. The four
major changes are: 1) In care facilities, where there are five or fewer persons receiving care
that are within a single family dwelling, they are permitted to comply with the International
Residential Code (IRC), but they are now required to have the building sprinkled with an
automatic fire sprinkler system. 2) In 2009, the IBC required windows in houses and
apartment buildings that were more than 72” above the exterior finished grade and the
lowest part of the clear opening of the window was less than 24”, the window could not
allow passage of a 4” sphere or there had to be devices to limit that. In the 2012 IBC, that
goes up to 36” above the finished floor on the interior. It will affect apartment buildings. 3)
Sprinkler systems will be required in factories exceeding 2,500 sq ft that are used to
manufacture upholstered furniture or mattresses. Mercantile occupancies exceeding 5,000
sq ft that display and sell upholstered furniture or mattresses need to have a sprinkler
system, and storage occupancies exceeding 2,500 sq ft used for storage of upholstered
furniture or mattresses require a sprinkler system. 4) Carbon Monoxide alarms will be
required in institutional and residential occupancies that have a fuel burning appliance or
are in a building that has an attached garage.
Another noted item is how they calculate structural. The outcome is not changed, but the
calculations are done differently.
Discussion was held regarding elevators to residential units, 1109.1. Nutini mentioned the
struggle for clients wanting first floor retail and second floor residential having to have
elevators – it is cost prohibitive for clients. Ripperger stated elevators are required for four
or more units up.
Ripperger referred to Chapter 5 of the Ames Municipal Code. Staff deleted Chapter 29, the
Plumbing section, during the last code adoption. This time staff left it in to use as a
reference for fixture counts. Ripperger also said staff clarified the requirement for frost
footings on exterior landings.
Nutini questioned the stricken language regarding foundations on p age 5-17. Ripperger
stated that it is just for clarification – they took out some unneeded language to clean it up.
Discussion was held about the need of engineered stamped plans and the table used. Nutini
stated that there is ambiguity with regards to what type of stamp is required and when.
Brad Heemstra asked what the remaining process was for the code adoption. Seana Perkins
provided a proposed schedule and City Council timeline.
Moved by Brandt, seconded by Heemstra, to accept the recommendations to the 2012 IBC
as amended by staff
Vote on Motion: 5-0
Motion passed unanimously
Page | 3
ii. International Residential Code (IRC) – Summary of significant changes by Craig Hageman.
Hageman stated that Chapter 5 has a lot of clean up and language revision, but not a lot of
substantial change. He referred to the 2012 IRC Code Update that was provided to the
Board noting there were not a lot of major changes. Some of the changes are: 1) A
requirement for a positive closer on door between house and garage. 2) Egress window
wells are required to have drainage somewhere out on the property or to the foundation
and drainage system. 3) A requirement for verifying ventilation in a house / getting some air
changes in a house. That can be done with a mechanical ventilator where it’s a separate
system or it may calculate out that all the local fans in the house will suffice for that air
exchange, i.e., bath fans, kitchen hood vents, anything that is vented to the exterior, any
ductwork that is coming from the exterior back into the building. A blower door test will
determine whether the air changes are happening or not. Heemstra asked if the blower
door test will be required. Hageman stated that it will be required in the 2012. It can be
performed by a third party, but it needs to have verification to the building department on
the outcome. Cormicle referred to R303.4.
Nutini asked about the status of fire sprinklers. Hageman said the State of Iowa is just
beginning their adoption process and they are going to amend out the requirement for
residential sprinklers again and we will follow that lead.
Hageman mentioned another significant requirement change that staff is going to
recommend amending out of this code cycle. It is the requirement for the protection of
floors even in unfinished basements. If there are TJI floor joists, for example, that would
need to be protected with half inch gypsum board throughout the entire basement except
for 80 sq ft around the mechanical area. Other jurisdictions are leaving the floor protection
requirement in even though they will amend out the residential sprinkler requirement. It is
section R501.3.
Hageman continued that the 2012 IRC has consolidated a lot of information about deck
construction into one section now. Another page on bracing with a simplified method on
wall bracing has been added, Section R602.12.
Hageman then addressed Chapter 5, Section R302.1, the addition of Exception #6: Walls of
detached garages and accessory structures greater than or equal to 3 feet from a property
line. The purpose of it is for clarification, so the chart will match our zoning or dinance. He
also pointed out that 18”x18” grid of #4 rebar in the foundation wall is now in Chapter 5
also.
Heemstra questioned R311.7.8.2 Continuity. Hageman stated that we are back to the 2009
version that states handrails may be interrupted at the point of transition from handrail to
guardrail on stairways open on both sides at the bottom of a flight of stairs.
Cormicle questioned R315.3 Where required in existing dwellings. Hageman said this
section now clarifies locations.
Page | 4
Hageman addressed R403.1 General. This lays out the specifications for concrete and
encased electrodes. This has been enforced for a number of years, but now we are adding it
to our local amendments.
Nutini asked what the city stance is on grounding on CSST. Hageman stated that it is
required in the fuel gas section of the IRC. It is also a requirement of Alliant Energy that it
must be in place before they will unlock a meter.
Heemstra asked for clarification on the blower door test. Is the blower door test required
or does one have to have a whole-house ventilation system if one does a blower door test
and are less than five? Hageman stated that a blower door test will be required. Heemstra
asked if it was on all homes in the city and questioned if that was happening now. Hageman
responded that the majority do. Heemstra stated that he is reading it differently. He is
hearing that blower door tests are required, but he is reading R303.4 that a whole-house
ventilation system is required when a blower door test is less than five. Hageman then
referred to R303.4 of the IRC, where the air infiltration rate of the dwelling unit is less than
five air changes per hour when tested with a blower door at a pressure of 2 inches of water
column in accordance with section N1102.4.1.2, the dwelling unit shall be provided with
whole-house mechanical ventilation in accordance with N1507.3.
Moved by Brandt, seconded by Nutini, to accept the staff recommended changes to the
2012 IRC
Vote on Motion: 5-0
Motion passed unanimously
iii. International Energy Conservation Code (IECC)
Seana Perkins stated that there is no synopsis. Staff is proposing adoption in its entirety.
Cormicle clarified that we follow state law on energy conservation.
Moved by Brandt, seconded by Heemstra, to adopt 2012 IECC as recommended by staff
with no local amendments
Vote on Motion: 5-0
Motion passed unanimously
iv. International Existing Building Code (IEBC)
Ripperger stated there are no significant changes to point out.
Moved by Heemstra, seconded by Brandt, to adopt 2012 IEBC as recommended by staff
with no local amendments
Vote on Motion: 5-0
Motion passed unanimously
Page | 5
v. International Mechanical Code (IMC) – Summary of significant changes by Mike
Makelbust. Makelbust stated there are no changes to the amendments or any significant
changes to the IMC. It addresses the air dispersion systems in commercial buildings, which
it has not done before. Cormicle asked if 5.206 of the city code was the only clarification
and otherwise it is in its entirety as written. Makelbust confirmed. The one issue is
referencing exceptions regarding duct systems..
Moved by Heemstra, seconded by Brandt, to adopt 2012 IMC with the noted revisions by
city staff in Chapter 5 Section 5.206
Vote on Motion: 5-0
Motion passed unanimously
vi. International Fuel Gas Code (IFGC) - Summary of significant changes by Mike Makelbust.
Makelbust stated that there are no significant changes. There are some new definitions.
Cormicle asked if 5.207 of the city code was the only clarification. Makelbust confirmed.
Moved by Brandt, seconded by Werstein, to adopt 2012 IFGC with the noted revisions by
city staff in Chapter 5 Section 5.207
Vote on Motion: 5-0
Motion passed unanimously
vii. Uniform Plumbing Code (UPC) - Summary of significant changes by Mike Makelbust.
Makelbust stated there are three significant areas that have changes: 1) In Section 605.0.12,
a sentence has been added that says “the service valve at the main unless a post indicator
valve (PIV) is required by the Fire Inspector”. It is making the post indicator valve
requirement an option now of whether or not the Fire Inspector will require it. The
following wording is simply moving information from different sections and putting all in
one location. When the PIV is not being used, it describes the service valves at the property
line. 2) In Section 904.1, a paragraph is being struck regarding each individual building or
structure having a main vent stack equal in size or larger than the required building sewer. It
is eliminating the requirement of one 3” plumbing stack. Now it can be accomplished with
multiple 2” stacks, which aligns us with the UPC. 3) Another change to align us with the UPC
is the deletion of the air admittance valve on an island kitchen or an island bar sink.
Moved by Brandt, seconded by Nutini, to approve the 2012 UPC with the amendments as
noted in Chapter 5 by city staff
Vote on Motion: 5-0
Motion passed unanimously
Perkins stated that a motion to adopt Chapter 5 was needed. Jessica Spoden clarified that
minor changes have been made to Chapter 5.
Moved by Brandt, seconded by Heemstra, to adopt Chapter 5 with the noted revisions
dated July 1, 2012
Page | 6
Vote on Motion: 5-0
Motion passed unanimously
viii. Chapter 8 Fire Code – Summary of significant changes to the International Fire Code
(IFC) by Tom Henriksen. Henriksen stated that the book has been reformatted, going from
46 chapters to 66, a lot having to do with hazard ous materials and special processes and
operations. Some of the significant issues are requirements for: rooftop items, emergency
lighting, textile and vinyl wall coverings, monitoring companies being required to notify the
local fire agency if there is a change in service of the facilities they monitor, and floor level
exit signs.
Cormicle asked why items 11-38 were deleted in Chapter 8 on pages 8-2 and 8-3. Shawn
Bayouth responded that the deletions referred to current structures. Even though the code
has become more complex and the number of businesses has increased substantially over
the years, there is still only one fire inspector on staff and it was determined that the items
were not being inspected. In trying to prioritize most effectively, while being mindful of
treating all businesses equally, staff decided to put the priority on occupancy structures and
new construction, thus setting behind some of the items that could be applied to current
structures. The code gives the ability to the authority having jurisdiction to notify any
businesses that don’t meet the standard and to provide them a time schedule to become
code compliant. The sections are written out now with the intention of bringing them back
in the future after staff has had a chance to determine how many structures would be
impacted, what the cost will be, and what kind of time schedule could be put in place that
could be agreeable to each business owner.
Moved by Heemstra, seconded by Brandt, to adopt Chapter 8 Fire Code as presented by city
staff dated September 1, 2013 which includes the adoption of the 2012 IFC
Vote on Motion: 5-0, with Nutini’s vote in writing
Motion passed unanimously
4. Board or staff comments
Cormicle asked to be notified if any Board members were needed to appear before City
Council. Perkins stated she will keep the Board informed.
5. Adjournment
Moved by Heemstra, seconded by Brandt , to adjourn the meeting at 6:21 p.m.
Vote on Motion: 4-0. Nutini left the meeting prior to the adjournment.
Motion passed unanimously
____________________________
Eileen Carter, Recording Secretary