HomeMy WebLinkAboutA001 - Council Action Form dated January 27, 2015 ITEM # 12
DATE: 01-27-15
COUNCIL ACTION FORM
SUBJECT: 2014 NATIONAL ELECTRICAL CODE
BACKGROUND:
The National Electrical Code (NEC), published by the National Fire Protection Association
(NFPA), is the model code of standards for electrical construction and maintenance in use
throughout the United States. The Code is updated at three year intervals to reflect the latest
improvements in public safety technologies. The State of Iowa, all major Iowa communities, and
the City of Ames regularly adopt the most recent edition of the NEC.
The State of Iowa has adopted the 2014 edition of the NEC, and it became effective on January
1, 2015. The City of Ames follows State adoption to assure consistency of State and local
standards. Electricians doing work within the City of Ames are required by their State licensure
to follow the NEC adopted by the State, which as of January 1, 2015, would be the 2014 NEC.
The City of Ames is currently regulated by the last adopted NEC, which is the 2011 version of
the code.
The first step in the code adoption process is an in depth review of the 2014 NEC by
Inspections staff. Staff receives not only the 2014 NEC code book, but also reference materials
that describe the significant changes between the 2011 and 2014 versions of the code.
Research is conducted with staff from other Iowa jurisdictions to understand their process and
any stumbling blocks that they encountered along the way. Once a thorough review is complete,
the process moves on to the City's Building Board of Appeals.
The Building Board of Appeals is a seven member board appointed by the Mayor with the
approval of the City Council. Each member is qualified by experience and training in matters
pertaining to building construction. The membership of the Board consists of the following
professionals:
• Licensed Architect
• Professional Engineer
• General Contractor
• Homebuilder
• Licensed Journeyperson or Master Electrician, or Electrical Contractor
• Licensed Journeyperson or Master Plumber, or Plumbing Contractor
• Licensed Master HVAC Technician, or Mechanical Contractor
The Building Board of Appeals is tasked with reviewing proposed text amendments to Ames
Municipal Code, Chapter 5, Building, Electrical, Mechanical and Plumbing Code. Proposed text
amendments are reviewed by the Board with a public hearing and recommendation to the City
Council.
On October 20, 2014, Inspections staff sent an e-mail to all contractors who have done
business with the Inspection Division over the past year to notify them of the proposed 2014
1
NEC adoption process, and to notify them that their attendance and input at the November 3,
2014, Building Board of Appeals meeting would be welcome.
The Building Board of Appeals held its public hearing on November 3, 2014. The Board then
passed a motion to recommend to the City Council approval of the 2014 NEC with the State of
Iowa exceptions and one local amendment. One local contractor attended the Board meeting
and did not provide input.
The proposed local amendment is the same amendment as was adopted by the City of
Ames with the adoption of the 2011 NEC. This amendment limits the use of nonmetallic-
sheathed cable in other than one- and two-family or multi-family dwellings. The State
adopted exceptions include the same two exceptions that were adopted with the 2011 NEC
which limits the requirements for ground fault circuit interruption (GFCI) receptacles in certain
instances where receptacles are not readily accessible or receptacles for appliances in
dedicated spaces. Three new exceptions were added by the State, two of which lessen the
requirements for arc fault circuit interrupters (AFCI) in certain existing situations, and the third
new exception is a clarification on compliance with the adopted International Energy Code.
SIGNIFICANT CHANGES:
Below is an overview of the significant changes of the proposed 2014 NEC from the
currently adopted 2011 code. Although this is not an inclusive list, it does highlight the
majority of new changes from the previous code cycle.
The following four new articles have been added to the 2014 NEC:
• Article 393- Low-voltage suspended ceiling power distribution systems
• Article 646- Modular data centers
• Article 728- Fire resistive cable systems
• Article 750- Energy management systems
The following are some changes in the 2014 NEC for single and multifamily dwelling units:
• Section 210.8(A)(7)will expand GFCI protection for all receptacles located within 6 feet
of dwelling unit sinks. This removes the words "located in areas other than kitchens"to
require GFCI protection for all 125-volt, single-phase, 15 and 20 ampere receptacles
installed within 6 feet of the outside edge of dwelling unit sinks (including kitchen sinks).
• Section 210.8(A)(10)will require GFCI protection for dwelling laundry area receptacles.
• Section 210.8(D) will require GFCI protection for dishwashers in dwellings.
• Section 210.12(A)will expand AFCI protection for all 120-volt, single-phase, 15 and 20
ampere branch circuits supplying outlets and devices in kitchen and laundry areas of
dwellings.
• Section 680.21(C)will require GFCI protection for all pool pump motors regardless of
amperage.
The following are some changes in the 2014 NEC for commercial and industrial projects:
• Section 110.26(C)(3) will lower the requirement for panic hardware on personnel doors
from 1200 amperes to 800 amperes.
2
• Section 110.26(E)(2)(a)&(b) will extend dedicated space requirements to outdoor
equipment.
• Section 210.64 will require a receptacle within 50 feet of all non-dwelling service
equipment.
• Section 590.4(J) will prohibit temporary branch circuits and feeders from being laid on
the floor or ground.
• Section 700.28 will require an engineer to design selective coordination for emergency
systems
ALTERNATIVES:
1. Set the public hearing for February 10, 2015, to review the proposed changes to the Ames
Municipal Code, Chapter 5 and the proposal to adopt the 2014 edition of the National
Electrical Code (NEC) with one local amendment and State of Iowa exceptions.
2. Direct staff to work with the Building Board of Appeals to develop further local amendments
to the recommended codes.
MANAGER'S RECOMMENDED ACTION:
The Building Board of Appeals has reviewed the proposal and has recommended approval to
the City Council. Therefore, it is the recommendation of the City Manager that the City Council
adopt Alternative No. 1, thereby setting a public hearing for February 10, 2015.
3
MINUTES OF THE REGULAR MEETING OF THE BUILDING BOARD OF APPEALS
AMES, IOWA NOVEMBER 3, 2014
Call to Order
The regular meeting of the Building Board of Appeals was called to order by Chairman Larry
Cormicle at 4:00 p.m., November 3, 2014, in Room 235 in City Hall, 515 Clark Avenue. Present
from the Building Board of Appeals were Larry Cormicle, Brad Heemstra, Larry Brandt, Nathan
Werstein, and Dan Nuntini.
Staff members present were Seana Perkins, Scott Ripperger,I! ick Patterson, and Jessica
Spoden. "t a
1k
Guests present were appellant Jeff Rains of BSB pesign, general contractor Keith Dallenbach,
two members of the Sigma Chi building committee;and an Krogmanift9m Kurrent Electric.
Moved by Heemstra, seconded by Brandt, to approve the mir,wes of July 7 2d 4
Vote on Motion: 5-0
aF P. ,
Motion passed unanimously
3
Old Business
None
New Business ;
A. Appeal of the Electrical code, NEC-2011 Section„334.10 and City of Ames local code
amendment 5.205 by Sigma;�Ghi Beta Omicron.
Jeff Rains gave a summa0,of the project.The history`of the amendment in place restricting the
use of metal cable primarily,refers`toicommerciaf structures. It is still allowed in multi-family
structures'although fraternity,houses donot fall under that category because they have
sleeping uni s�no_t dwelling units.The code''defines a dwelling unit as a sleeping unit with a
kitchen. The Sigma Chi sleeping L 4nits have a space for a microwave and small refrigerator but
not a range, so based;ion this, th%electrical code classifies the fraternity as an "other structure"
which was eliminated by,thel,adoption of the City of Ames amendment. Since the fraternity is a
residential use, and the appellant believes the intent of the amendment was to limit the use of
metal cable in commercial structures,they are asking for the ability to use metal cable in this
application.
Steve (keith?) Dallenbach stated that this is a financial hardship for the fraternity. The project is
being funded by donations from alumni and the cost to have use NM cable is close to$20,000.
Rains added that their electrician suggested using metal cable in the kitchen area.
1
Seana Perkins reviewed the steps taken by the City regarding the Code Modification request.
The definition of fraternity does not meet the exemption criteria. Our local amendment 5.205
prohibits the use of metal cable in this type of application, so the City denied the request.
Brad Heemstra stated that there have been many discussions over the years about upgrading
fraternities and sororities for safety, but as a City we have chosen not to allow romex in
fraternities. He asked how long this policy has been in place.
Nick Patterson stated that the City of Ames adopted this particular amendment in 2002 and it
has gone through several code adoptions. Inspections over the5y_ears of fraternities and
sororities have shown more wear and tear and abuse than other residential properties.
Dallenbach stated that exceptions have been issued to''„Greek housing for multiple reasons
usually based on economic conditions as non-profits:-The economiGsituation of a donated
building for residences is worth considering Is this a hardship being placed on fraternities and
sororities? He is not concerned about abuse this new building or this berg a building that
can't take abuse.The walls will be built in a way"that kmakes the,building rriore�durable to
address those concerns.
Jessica Spoden confirmed that economic hardship has be6Wajeason for other variances that
have been issued by the City.
It 4J,{ .E,k
k �s{
Cormicle asked if the,other variances were for,,life safety i yes or appearance and zoning.
Sponden clarified that°they have'not been forlife'safety.
iw
Dallenbach does not ievq,that,-rorheXrr mex,has been proven to be a dangerous product.
Rains stated that the'owner is concerned about;fhe original intent of the code. Commercial
applications are understandable, but;this is a residential project.
IJ
Brandt asked: many fraternities or sororities are currently involved in major construction
and have they filed,for variances?{;The City has not allowed romex in commercial buildings since
the 1950's.
Spoden stated that another fraternity has received a variance for their parking requirement s.
Rains again stated that this project is not a commercial building. Brandt countered that it is the
equivalent of a boarding house.
Discussion was held about cooking units and heating elements.
Heemstra reiterated that since 2002 other Greek houses have had to use metal cable in similar
situations. He then asked for clarification on whether it was the City's intent in 2002 to not
allow romex in fraternities. What prompted the decision at that time?
2
Brandt stated that the code changed allowing romex to be in some type III, IV, and V
construction, which prompted the decision by the City not to go along with it.
Nathan Werstein asked about the timing of this decision in relation to the adoption of the 2014
NEC. Spoden stated that the 2014 NEC will not be in effect until January 2015 and this project is
underway now.
Heemstra expressed concern about pulling out one project and changing direction on a code
that has been in effect since 2002. '
Moved by Brandt, seconded by Heemstra,to deny the,apppal
"
Vote on Motion: 5-0
`
Motion passed unanimously
ry ' ,Ir'rc
'"CIRJ O,
B. 2014 NEC Code Adoption ,
Perkins presented the proposed timeline for the'12014 NEC code adoption: $ teading and
public hearing November 25, 2014; 2 reading Decembeq?;I2014; 3 readin ' cember 23,
2014. Adoption date would be effectN ,f� anuary 1, 20151�o lign the City of Ames with the State
of Iowa adoption process.The State of1,loviraiwill likely have!exceptions to the 2014 NEC. In the
,, i
memo to the Board, staff laid out optionsifor the Board to conMder. One option is to adopt the
2014 NEC straight up with our'local amend.,ents The-second option is to follow the State of
Iowa and adopt it following'their,exceptions and our Jocal am ndments.
"g
r #,iai ,r
Heemstra asked how the Board willl'know what the State exceptions are.Will the Board circle
back on the State exceptions? Is the memo suggesting the Board just adopt what the State does
when they do not know what the,State isgoing to do?,Will the Board revisit what the State has
decided2 a.
Perkins stated that one of tle;�o tions isau:.s. t to adopt what the State adopts assuming that the
State is going through the process and will choose the exceptions that are right for the State of
Iowa and the City of Ames would,trust that.
Ripperger stated that no matte`r.wlhat the State does, the City of Ames is still bound by the State
code. We can make it more restrictive, but we cannot make it less restrictive.
Spoden concurred by saying the State would not be making the NEC more restrictive, if
anything,they would be making it less restrictive. Spoden also stated that if the State was to
make changes at a later date, those changes would automatically be adopted by the City code.
Discussion was held on the state adoption. Spoden stated that the State is not required to
adopt the National Electrical Code. The history of the State has been to make the code less
restrictive.
3
Cormicle and Heemstra questioned if the City of Ames was going to accept the less restrictive
stance that the State adopts. Should the Board wait to adopt the 2014 NEC until after the State
has adopted it to see what exceptions they have adopted? If the State makes the code lenient,
the Board can reconvene and subsequently adopt local ordinances.
Moved by Heemstra, seconded by Nutini,to adopt the 2014 NEC with the State of Iowa
exceptions and our local amendment
Vote on Motion: 5-0
Motion passed unanimously
Board Comments
None «...
s�$4
P I '�'ti
II IIEI
Adjournment '`
The Board adjourned at4:43pm �"' {., c 'air. ; _
'!
r
Eileen Carter, Record ing_Secretary �l� �'�� U�
J t r"I r Nr liii{4�`I
v
4
Ames Municipal Code Chapter 5 - EXCERPTS
Sec. 5.100.TITLE &ADOPTION.
(11) Electrical. The National Electrical Code,2844-2014 edition, published by the National Fire
Protection Association, One Batterymarch Park, Quincy, Massachusetts, awed
is hereby adopted as the electrical code of the City
of Ames and shall govern electrical work and installations in the City of Ames, except for
such specific, higher standards and requirements as have been or may from time to time
be enacted by the City of Ames.
Sec. 5.205. ELECTRICAL.
The provisions of the National Electrical Code (NEC), :2011 2014 edition, are hereby amended
as follows:
(1) Section 334.10, Nonmetallic-Sheathed Cable, Uses Permitted, ef the said Natiena
F!eGtF!^Gede is amended by deleting Subsection(3)therefrom and inserting in lieu thereof
a new Subsection (3): All other structures shall be wired using other methods as allowed by
the NEC.
(2)Add the following exceptions to Article 210.8(A)(2),paragraph (A), subparagraph(2)
Ground-Fault Circuit-Interrupter Protection for Personnel, Dwelling Units :
(a) Exception No. 1404�: Receptacles that are not readily accessible.
(b) Exception No. 249424: A single receptacle or a duplex receptacle for two appliances
located within dedicated space for each appliance that, in normal use, is not easily
moved from one place to another,and that is cord-and-plug connected in accordance
with 400.7(A)(6), (A)(7), or(A)(8).
(c) Receptacles installed under the exceptions to 210.8(A)(2) shall not be considered as
meeting the requirements of 210.52(G).
(3) Add the following exceptions to Article 210.8(A)(5), Ground-Fault Circuit-Interrupter
Protection for Personnel, Dwelling Units4A)(5):
(a) Exception No. 24e-(5): Receptacles that are not readily accessible.
(b) Exception No. 34e45): A single receptacle or a duplex receptacle for two appliances
located within dedicated space for each appliance that, in normal use, is not easily
moved from one place to another and that is cord-and-plug connected in accordance
with 400.7(A)(6), (A)(7), or(A)(8).
(c) Receptacles installed underthe exceptions to 210.8(A)(5) shall not be considered as
meeting the requirements of 210.52(G).
(4) Delete section 210.12(B), Arc-Fault Circuit-Interrupter Protection, Branch Circuit
Extensions or Modifications—Dwelling Units.
(5) Delete exception to section 220.12, Lighting Load for Specified Occupancies,and
insert in lieu thereof the following exception:
Exception: Where the building is designed and constructed to comply with an energy
code adopted by the local authority, the lighting load shall be permitted to be
calculated at the values specified in the energy code.
(6) Delete section 406.4(D)(4), General Installation Requirements, Replacements,Arc-
Fault Circuit Interrupter Protection.