Loading...
HomeMy WebLinkAbout~Master - Adopting New Plumbing Code ORDINANCE NO. 3198 AN ORDINANCE TO AMEND THE MUNICIPAL CODE OF THE CITY OF AMES, IOWA, BY REPEALING CHAPTER 21; ENACTING A NEW CHAPTER 21 ON PLUMBING REGULA- TIONS; ESTABLISHING A PENALTY; REPEALING ALL ORDI- NANCES OR PARTS OF ORDINANCES IN CONFLICT HERE WITH; AND ESTABLISHING AN EFFECTIVE DATE. BE IT ENACTED, by the City Council for the City of Ames, Iowa: WHEREAS, by enactment of Ordinance No. 2680 on October 25, 1983, the City of Ames became subject to the State Building Code pursuant to section 103A.12 Code of Iowa; and, WHEREAS, it is now desired to withdraw from application of the State Building Code and enact the Uniform Plumbing Code, 1988 Edition, with modifications, along with the state handicapped access regulations, energy efficiency regulations and factory built structures regulations, by reference; and, WHEREAS, notice has been published and public hearings held as re- quired by law. NOW, THEREFORE, BE IT RESOLVED, by the City Council of the City of Ames, Iowa: Section One. The Municipal Code for the City of Ames, Iowa shall be and is hereby amended by repealing Chapter 21 and enacting a new Chapter 21 as follows: "CHAPTER 21 PLUMBING DIVISION I. ADOPTION Sec. 21.101. PLUMBING RULES AND REGULATIONS The Uniform Plumbing Code, 1988 Ed. Published by the International Association of Plumbing and Mechanical Officials, (herein called UPC), Chapters 1-13, Appendices C-D shall be the plumbing code for the City of Ames, Iowa, except for such modifications, additions or deletions as hereinafter enacted. DIVISION II. ADMINISTRATION See. 21.201. PERMITS. (1) Permit required. It is necessary to obtain a plumbing permit whenever any installation, extension, connection or addition to the plumbing system of a building or to the private sanitary sewer, or private water supply C 1 9-17-92 system is made in the city, except as hereinafter provided. (2) Application for permit. An application shall be made in writing at the inspection division on the form provided by the city, along with such plans as may be required by the Building Official. Only registered plumbing contractors may apply for a plumbing permit, except that permits are not required for public water mains or public sewer mains. (3) Issuance of permit. Upon approval of the application by the inspector and approval of the plans and specifications if required, the permit shall be issued and a record thereof retained in the inspection division. (4) When permits not required. No permit will be required for the repair of faucets or closet tanks, or for replacing a valve when used for the same purpose, or for forcing out stoppages in soil and waste pipes, or for repairing leaks in distribution piping if there is no change in any form from the existing location and the pipe being replaced was of adequate size to carry the unit fixture load. Permits are not required for public water mains or public sewer mains. (5) Permits required for additional work. When a plumbing permit has been issued for plumbing work, no additional work not included in the permit may be undertaken or additional fixtures set, until the permit has been amended to include the additional work. Any additional permit fees shall be calculated in the same manner as though the total value of the permit was calculated at one time. (6) Expiration of permits. When a permit has been issued to do plumbing work, such work shall be started within one hundred eighty (180) days from date of the permit, and be completed within one year after beginning the work, otherwise such permit is null and void and a renewal of such permit must be obtained. (7) Work commenced without permit. It shall be unlawful for any person, firm or corporation to make any installation, extension, connection or addition to the plumbing system of a building or to the private sanitary sewer, private storm sewer or private water supply system in the city without first obtaining a permit to do so. This provi- sion shall not apply to emergency work when it shall be proved to the satisfaction of the inspector that such work was urgently necessary and that it was not practical to apply for a permit before commencement of the work. In all such cases, a permit must be obtained as soon as it is practical to do so. C 2 9-17-92 Sec. 21.202. INSPECTION, TESTS AND ENFORCEMENT. (1) Supervision of the work. When a permit has been issued for plumbing work, the doing of such plumbing shall be under the direct supervision of a journeyman plumber at all times. Only journeymen plumbers identified on the registration of a given contractor will be recognized as able to supervise work done for that contractor. (2) Authority of inspector. The inspector or authorized representative shall have authority to enforce the provisions of this chapter relating to the installation and testing of all plumbing. The inspector may revoke said permit or issue a municipal infraction at any time when such work is not being done in accordance with the provisions of this chapter or the approved plans and permit; and if such permit is revoked, it will be unlawful for any person to proceed further with said work without approval of the inspector. (3) Right to inspect. The inspector or authorized rep- resentative shall have access to any building or upon any premises, at any reasonable time, when it is necessary to make an inspection to enforce the provisions of this chapter or when the inspector has reasonable cause to believe that there exists a condition which makes such building or premises unsafe or insanitary. (4) Destroying posted notices. It shall be unlawful for any person to willfully mutilate, deface, remove or destroy any certificate or notice placed by the inspector in any building in regard to the plumbing work in said building until authorized to do so by the inspector. (5) Notice of final inspection. It shall be the duty of the person doing the work authorized by the permit to notify the inspector, orally or in writing, that said work is ready for inspection. It shall be the responsibility of the permittee to ensure that access is provided such that an inspection can be made. Upon the satisfactory completion and final test of the plumb- ing system a notice of final inspection, with the signature of the plumbing inspector thereon, will be posted in a suitable place in the building and a record of such final inspection retained in the inspection division. (6) Installation Inspection. Under no circumstances shall plumbing installations be backfilled prior to inspection. Work backfilled prior to inspection shall be uncovered by the plumber doing the work. Rigid pipe installations shall be such that all pipe joints are visible with backfill placed only to stabilize the pipe position prior C 3 9-17-92 to inspection. Flexible pipe shall have no more backfill placed than to the middle of the pipe prior to inspection. Following inspection and approval, the rigid pipe installation may be backfilled with approved materials. Following review of the flexible pipe installation, the inspector shall observe the placement of select rock backfill to a point 6" over the pipe. Following approval of the initial backfill, the remaining backfilling operation may continue using approved materials. C 4 9-17-92 Sec. 21.203. FEES (1) Fees pertaining to this chapter shall be in such amounts as shall be established from time to time by resolution of the city council. (2) A special fee, as set by the City Council, shall be charged for installation of plastic pipe to cover all costs of the inspection of its installation if the time required exceeds the inspection time of other pipe installations. DIVISION III. LICENSES/REGISTRATION Sec. 21.301. DEFINITIONS The following definitions of terms shall be used in the interpretation of this chapter: (1) Apprentice Plumber. An apprentice is an employee of a registered plumbing contractor who while learning the trade of plumbing, is assisting in the installation, alteration or repair of plumbing systems or parts thereof and while engaged in such work is in the presence of and under the direct supervision of a licensed journeyman plumber. (2) Journeyman plumber. A journeyman plumber is a person who through training and experience has acquired the requisite skill and knowledge necessary for the proper installation, alteration and repair of plumbing systems or parts thereof and who holds a valid license as a journeyman plumber from the city. A journeyman plumber shall have had at least four years' experience as an apprentice plumber. (3) Master plumber. A master plumber is a person engaged in the business of plumbing, other than a journeyman plumber engaged in the actual installation, alteration and repair of plumbing, and who is skilled in the planning, supervising and practical installation of plumbing systems or parts thereof and is familiar with the laws, rules and regulations of the city and the State of Iowa governing the same and who holds a valid license as a master plumber issued by the city. (4) Plumbing Contractor. An individual, firm, or corporation which performs services doing plumbing installation. Sec. 21.302. REGISTRATION. Before doing any plumbing business in the city, a plumbing contractor shall be registered with the City Inspection Department. C 5 9-17-92 (1) Conditions for Registration. A plumbing contractor shall meet both of the following requirements as a condition of registration: (A) Each plumbing contractor shall have at least one licensed master plumber employed by or working for the contractor at all times. (B) Each plumbing contractor shall have at least one licensed journeyman plumber employed by or working for the contractor at all times. (2) Information to be provided. An applicant for plumbing contractor registration under this section shall provide to the Plumbing Inspector the following information: (A) The complete name, complete mailing address, street address and telephone number of the firm or corporation. (B) The name, position and private mailing address of a manager or general agent of the firm or of each officer of a corporation and the registered agent for service of legal process on the corporation. (C) The name, position and private mailing address of a person who is authorized to bind the firm in legal agreements. (D) If the registration is to be as an individual only, the name and mailing address, street address and telephone number of the individual. (E) The State Division of Labor registration number. (F) Every registrant shall carry Contractor's Commercial General Liability insurance in not less than $500,000.00 combined single limit and shall provide proof of coverage to the Building Official before registration. (G) The names of all master plumbers employed by or working for the plumbing contractor. (H) The names of all journeyman plumbers working for the plumbing contractor. (I) The names of all apprentice plumbers employed by or working for the plumbing contractor. (J) Other technical data and information pertaining to the work to be done as may be required by the Building Official. C 6 9-17-92 Every Registrant shall provide the required information accurately and completely. Any changes in the required information shall be reported to the office of the Building Official within ten (10) days from the date the information previously supplied has become inaccurate for any reason. (2) Plumbing Inspector Shall Respond. After application for registration has been received by the Inspector, the Inspector shall act promptly to issue the registration or to determine on what basis the registration may not be issued. The Plumbing Inspector shall so respond not later than two weeks following application. (3) Expiration and Renewal of Registration. Registration shall expire annually on January 1 and may be reactivated so long as the registration information remains accurate and proof of continued liability coverage is submitted. (4) Transfer of Registration is Prohibited. No registrant under this section shall allow their registration by name or other identification to be transferred or assigned to or in any manner directly or indirectly used by any person, firm or corporation other than the one to whom issued, for any purpose. (5) Registration Suspended. The Plumbing Code Board of Appeals shall have the authority to suspend any registration issued under this section for any of the following acts by the Registrant: (A) Continued work after the issuance of a stop order. (B) Initiating work in violation of the Board's decision or prior to the Board's decision. (C) Causing or permitting the unauthorized or prohibited use of a valid registration, by another, such as to allow the rights and privileges of registration to be applied to one not duly registered. (D) Judgment entry of two (2) violations of any of the provisions of this chapter committed within a period of twelve (12) consecutive months. Such suspension of registration shall be for a time not to exceed six (6) months. After expiration of such period of time as the Board shall have designated, and after payment of any outstanding penalties, costs, fees and proof of compliance and routine renewal fee, if it has become due in the interim, the suspended registration shall again become valid and effective. C 7 9-17-92 (6) Registration Revoked. The Plumbing Code Board of Appeals shall have the authority to revoke any registration issued under this section for: (A) A violation constituting the practice of any fraud or deceit in securing (a) a license or (b) a permit. (B) Three (3) violations of this chapter committed within a period of twelve (12) consecutive months. Such revocation of a registration by the Board shall be full and final cancellation of such registration, made effective on the date of the Board's decision. Any Registrant so judged by the Board shall not, thereafter, be allowed to be registered again in the City. (7) Suspension or Revocation Hearing. In considering allegations under this section regarding suspension or revocation of a registration, the Board of Appeals shall proceed upon sworn information furnished it by an official of the City, or by any person. Such information shall be in writing and shall be duly verified by the person familiar with the allegations made. The Board shall issue an order setting the matter for hearing at a specified time and place, and the Secretary of the Board, with the advice of the City Attorney, shall cause a copy of the Board's order, and of the allegations, to be served upon the Registrant by registered mail at least fifteen (15) days before the date set for the hearing. The Registrant may appear in person or by counsel at the time and place named in the order and present his/her defense to the Board. The City Attorney shall provide counsel for the Board. If the Registrant fails or refuses to appear, the Board may proceed to hear and determine the allegations in his/her absence. If he/she admits the allegations, or if, upon a hearing, the Board finds any of the allegations to be true, it may enter an order suspending or revoking the registration. Suspension or revocation resulting from a decision of the Board shall preclude the Registrant from securing a permit for work controlled by that registration in the city, or from becoming so registered under alternated identification, as long as the suspension or revocation is in effect. Sec. 21.303. PLUMBING LICENSES It is the purpose of this section to provide for the examination and licensing of journeyman and master plumbers in order to protect the public from hazard to life and property that might arise from improper installation of plumbing systems. C 8 9-17-92 (1) Application for License Required. Each applicant for a license either as a Journeyman or Master Plumber shall fill out and file, an application for license on forms furnished, submit proof of at least 4 years of apprenticeship to a licensed Journeyman Plumber and pay the required testing fee. Prior to testing the application shall be reviewed and approved by the Plumbing Inspector. Should the accuracy of the application be questioned, the board of appeals shall render its judgment in the matter. (2) Notice of Examination. When an application for a plumbing license has been filed and the applicant has been approved to take the licensing examination, the Secretary of the Board of Plumbing Examiners and Appeals shall notify the applicant of the place and time where the examination will be held. (3) Authorization to Issue License. Upon passage of the licensing examination, the applicant shall pay a licensing fee as set by the city council and a license shall be issued. (4) Licenses Not Transferable; Expiration, Renewal; Fee. Licenses are not transferable. Licenses shall be issued biennially and shall expire on the thirty-first day of December of the second year. Licenses may be renewed upon the payment of a reasonable fee set by the City Council to cover cost of administration. Failure to renew a license before the expiration date may subject the person to a new examination, except on recommendation of the Board, for good cause shown, the examination requirement be waived. (5) Recognition of Licenses from Other Cities. The board of plumbing examiners may without examination issue a license to any plumber holding a license from another city recognized by the board as having similar licensing standards. The board shall adopt written procedures for determining that the licensing standards are similar and shall maintain records of those cities for which plumbing licenses shall be recognized. (6) Licenses to be shown. Licenses shall be carried at all times while engaged in plumbing work in the City of Ames. At the Inspector's request licenses must be shown. (7) License Suspension. The Plumbing Code Board of Examiners & Appeals shall have the authority to suspend the license of any plumber for any of the following acts: C 9 9-17-92 (A) Judgment entry of two (2) violations of any of the provisions of this chapter committed within a period of twelve (12) consecutive months. Such suspension of license shall be for a time not to exceed six (6) months. After expiration of such period of time as the Board shall have designated, and after payment of any outstanding penalties, costs, fees and proof of compliance and routine renewal fee, if it has become due in the interim, the suspended license shall again become valid and effective. (8) License Revocation. The Plumbing Code Board of Examiners & Appeals shall have the authority to revoke the license of any plumber for any of the following acts: (A) Any fraud, deceit or misrepresentation in the application or examination for a plumbing license. (B) Judgment entry of three (3) violations of any of the provisions of this chapter committed within a period of twelve (12) consecutive months. Such revocation of a license by the Board shall be full and final cancellation of such license, made effective on the date of the Board's decision. Any Licensee so judged by the Board shall not, thereafter, be allowed to be registered again in the City. (9) Suspension or Revocation Hearing. In considering allegations under this section regarding suspension or revocation of a license, the Board of Appeals shall proceed upon sworn information furnished it by an official of the City, or by any person. Such information shall be in writing and shall be duly verified by the person familiar with the allegations made. The Board shall issue an order setting the matter for hearing at a specified time and place, and the Secretary of the Board, with the advice of the City Attorney, shall cause a copy of the Board's order, and of the allegations, to be served upon the licensee by registered mail at least fifteen (15) days before the date set for the hearing. The licensee may appear in person or by counsel at the time and place named in the order and present his/her defense to the Board. The City Attorney shall provide counsel for the Board. If the licensee fails or refuses to appear, the Board may proceed to hear and determine the allegations in his/her absence. If he/she admits the allegations, or if, upon a hearing, the Board finds any of the allegations to be true, it may enter an order suspending or revoking the license. Suspension or revocation resulting from a decision of the Board shall preclude the licensee from doing any plumbing work in C 10 9-17-92 the city as long as the suspension or revocation is in effect. Sec. 21.304. EXEMPTION FOR HOMEOWNER. No such license or registration procedure shall be required for alteration or repair work to be performed on a single family residential structure when the person performing the alteration or repair work is the owner of the structure, and has his/her legal residence there. The homeowner shall be automatically termed a Licensee/Registrant for the purposes of such a project. Notwithstanding such relief from licensing/registration, all requirements for permits for the work shall remain in force. DIVISION IV. PLUMBING BOARD Sec. 21.401. PLUMBING BOARD CREATED; MEMBERSHIP, APPOINTMENT; QUORUM; AUTHORITY There is hereby created a Board of Plumbing Examiners and Appeals, of three (3) members, at least one of whom shall be a Master Plumber and one shall be a Journeyman Plumber and one shall be either a Master or Journeyman Plumber, appointed by the mayor and approved by the city council. Two (2) of the board members shall constitute a quorum for the transaction of business. The plumbing inspector employed by the city shall be a member ex officio of the board without voting power. The board has the responsibility and authority to: (1) Approve areas to be administered. (2) Act as a board of appeals to hear appeals from decisions of a plumbing inspector when it is claimed that the true intent of the plumbing code has been incorrectly interpreted, the provisions of the code do not apply, or an equally good or better form of construction can be allowed. (3) The board shall review proposed changes to this chapter and make recommendation to the city council. (4) The board shall adopt, from time to time such rules and regulations as it may deem necessary to carry into effect the board's duties as set out in this chapter. The board shall have no power to waive any provision of this code. The board shall have no authority over activity within city right-of-ways or easements. This authority is reserved to the Director of Public Works. The board shall have no authority over the sizing of water meters, this authority is reserved to the Director of Water and Pollution Control. C 11 9-17-92 Sec. 21.402. DATES OF BOARD MEETINGS The Board shall meet upon notice of the chairperson of the board within ten (10) days of the filing of an appeal or for other necessary business. Sec. 21.403. COMPENSATION OF BOARD. The members of the board of plumbing examiners shall serve without compensation. Sec. 21.404. TERM OF OFFICE OF BOARD. The term of office of the members of the board of plumbing examiners shall be three (3) years and they shall serve until their successors are appointed. The terms begin on April first of the year of appointment. No member shall serve more than two consecutive terms. Sec. 21.405. OFFICERS OF BOARD. The board shall annually select one of its members to act as chairperson, and one to act as vice chairperson. Records of the board shall be maintained in the office of the plumbing inspector. The inspector shall assist the board in preparing and conducting examinations. Sec. 21.406. APPEALS FROM INSPECTOR'S DECISION (1) Any person aggrieved by a decision of the plumbing inspector affecting interpretation may request and shall be granted a hearing on the decision provided that within 15 days after the date the person received notice of the decision, an application is filed with the Inspection Division, setting forth a brief statement of the grounds for appeal. Upon receipt of the request, the inspector shall give the petitioner written notice thereof at least three days before the date set. (2) All hearings shall be public, in accordance with the laws of the State of Iowa relating to government agency meetings. The hearing shall be held in accordance with rules adopted by the board and city council. At the hearing the appellant and/or agent shall be given an opportunity to be heard. The inspector shall have an opportunity to show why his/her decision should be affirmed. All interested persons shall be given an opportunity to be heard. Sec. 21.407. DECISION After a hearing, the board shall affirm, modify or overrule the decision of the inspector. Every action of the C 12 9-17-92 board shall be reduced to writing, stating its findings and reasoning, and signed by the chairperson. The decision shall be promptly filed and sent to the appellant. Sec. 21.408. ENFORCEMENT OF DECISION The city inspector shall take immediate action to enforce the decision of the board. Sec. 21.409. CODE AMENDMENTS. (1) Authority - the Plumbing Code Board of Appeals shall review and make recommendation on any and all proposed changes to this code. Recommendations shall be forwarded to the City Council for final action. (2) Philosophy - It shall be the philosophy of the City that the local code should follow as closely as possible the national standards as established by the Uniform Plumbing Code. (3) Procedure for Amendment (a) Any proposed change to this chapter shall initially be brought to the board of appeal for public hearing and recommendation to the City Council for final action. (b) Written notification of proposed changes shall be given to individuals registered with the City prior to the public hearing before the board. DIVISION V. AMENDMENTS, ADDITIONS AND DELETIONS Sec. 21.501. The provisions of the UPC for the City of Ames are modified as follows: (1) Add to Section 103 UPC this definition for 'building storm drain': a building (house) storm drain is a building drain used for conveying rain water, surface water, ground water, or other similar discharge exclusive of sewage and industrial waste to a building storm sewer. (2) Add to Section 103 UPC this definition for 'building storm sewer': a building (house) storm sewer is a building sewer which conveys the discharge of a building storm drain to a public storm sewer, or other point of disposal. (3) Add to Section 120 UPC this definition for 'subsoil drain': a subsoil drain is a drain which receives only C 13 9-17-92 subsurface or seepage water and conveys it to a place of disposal. (4) Add to Section 120 UPC the definition of 'sump service line': A sump drain line from the sump pit to the city storm sewer main. (5) Amend Section 203(a) and (b) UPC to read as follows: (a) Copper tube for underground drainage and vent piping shall have a weight of not less than that of copper drainage tube type IV". (b) Copper tube for above-ground drainage and vent piping shall have a weight of not less than that of copper drainage tubing Type M. EXCEPTION: Type DWV PVC may be used in one-and two-family dwellings. (6) Amend Section 203(d) UPC to read as follows: Copper tube for water piping shall have a weight of not less than Type M. EXCEPTION: Underground water piping shall have a weight not less than Type K copper tubing. (7) Amend Section 303(a) UPC by adding the following: More than one connection to a public sewer may be allowed by the Administrative Authority. (8) Delete Section 317(a) UPC and insert in lieu thereof the following provisions on Plumbing Excavations and Trenching: (a) Responsibility for protecting the public. The plumbing contractor shall without further or other order, provide, erect and maintain at all times during the progress and suspension of the work and until final completion thereof and removal of all obstruction occasioned by the work within the street limits, suitable and requisite barriers, signs or other adequate protection and shall maintain such warning lights, barricades or watchmen as may be necessary, to insure the safety of the public. Signs used shall conform to the most recent edition of the Iowa Manual on Uniform Traffic Control Devices. (9) Amend Section 317 UPC by adding new subsections (e), (f), (g) and (h) as follows: C 14 9-17-92 317(c) Excavations within street limits. It shall be unlawful for any person, firm or corporation doing plumbing work to begin any excavation or pavement cut or to place any obstructions within the limits of any street, avenue, alley or public place within the corporate limits of the City of Ames, Iowa without first having made application to the city and receiving a permit therefore. All matters pertaining to the cutting of pavement or excavation and filling of trenches and ditches within the limits of streets and alleys shall be in accordance with the provisions of the city ordinances relating thereto. 317(f) Backfilling building service ditches. The city or the plumbing contractor, at the City's option, will backfill all service ditches and excavations within the limits of all streets, alleys and public places within the corporate limits of the city. The plumbing contractor shall notify the city when such ditches or excavations are ready for backfilling and the city will fill the same as promptly as possible thereafter, or will permit the contractor to backfill. The plumbing contractor, if allowed to backfill, will maintain a two-year maintenance bond on the backfill, payable to the city. The responsibility of the plumbing contractor for the maintenance of warning lights, barricades or other protection shall cease when the city begins the work of backfilling the ditch or not later than the end of the next working day, excluding Saturday, Sunday or holidays, from the time of the receipt of written notification by the city that the ditch is ready for backfilling. The city will charge the plumbing contractor for such backfilling work in accordance with such schedule of fees and rates as shall from time to time be promulgated by resolution of the city council. All other ditches outside public areas shall be backfilled by the plumber as specified in 317(d) . 317(g) Manufactured Plug Required. All water, sanitary sewer, and foundation drain service lines shall be plugged with a water-tight manufactured plug when left unattended during installation. In this instance, unattended shall mean for any time period greater than one hour. No cast iron blind plugs shall be used. The following are approved caps: Dearborn No. 3412, Ecno plug, IPS Corporation, S402 Water Tite; Cherne, Part No. 270-245-Bell; Cherne, Part No. 270-296-4" J.D. . 317(h) Dry Ditch Required. The contractor will install the water, sanitary sewer, or foundation drain service lines in a 'dry ditch'. If necessary, the contractor shall over-excavate, furnish and place 1" concrete stone and provide necessary pumping equipment to maintain dry working conditions. Under no conditions shall the C 15 9-17-92 contractor discharge surface or groundwater to the sanitary sewer system or install water or sanitary sewer service lines in standing water unless on-site authorization is given by the inspector. The generally accepted understanding of a "dry ditch" is a work area without standing water and without flowing mud. Failure to have or provide adequate dewatering equipment shall not be accepted as justification for waiver of the 'dry ditch' requirement. (10) Amend Section 318(8) UPC by adding subsections (a), (b) and (c) as follows: 318(8)(a) No building moved into the city shall be connected to the city sewer or water system until the plumbing in such building has been inspected by the plumbing inspector and found in compliance with this chapter. (b) When a building is moved from one location to another within the city, no additional plumbing work or connection to the sanitary sewer or water utility will be done until the plumbing in said building has been reconstructed to comply with this chapter and tested. (c) When an area is annexed to the city, buildings in the annexed area will not be connected to the city water and sewer service until the plumbing of the building is inspected and brought into compliance with the requirements of this chapter. (11) Amend Section 320 UPC by adding a new paragraph as follows: Service Line Abandonment. Whenever an individual service line is permanently abandoned, the service line shall be physically disconnected as described below. The service shall be considered to be abandoned when a permit is issued for a new or replacement service for that property. Service shall also be considered to be abandoned when a service has been inactive or unused for six months, unless an extension is granted in writing by the City. The service line shall be physically disconnected within 30 days after abandonment. The water service shall be disconnected at the corporation cock on the main. Sanitary sewer and foundation drain service lines shall be disconnected at the curb on paved streets with a manufactured plug. All service abandonments shall be inspected by the Engineering Division of Public Works. (12) Delete Section 401 UPC and insert in lieu thereof the following: C 16 9-17-92 (a) Drainage piping shall be cast iron, copper, brass, ABS, PVC, extra strength vitrified clay pipe, or other approved materials having a smooth and uniform bore, except that: (1) ABS and PVC DWV piping installations shall be limited to those structures where combustible construction is allowed. (2) No vitrified clay pipe or fittings shall be used above ground or where pressurized by a pump or ejector. They shall be kept at least twelve (12) inches (.3m) below ground. (b) Drainage fittings shall be of cast iron, brass, copper, ABS, PVC, vitrified clay, or other approved materials having a smooth interior waterway of the same diameter as the piping served and all such fittings shall conform to the type of pipe used. (1) Fittings on screwed pipe shall be of the recessed drainage type. Burred ends shall be reamed to the full bore of the pipe. (2) The threads of drainage fittings shall be tapped so as to allow one fourth (1/4) inch per foot (20.9 mm/m) grade. (13) Amend Section 406 UPC by adding a new subsection (1) as follows: Cleanouts shall not be more than 40 feet apart in horizontal drainage lines of 2 inches in diameter or less, more than 90 feet of developed length apart in lines of 3 inches or larger. There shall be an entrance cleanout. A cleanout shall be provided in each vertical waste or soil stack at a point at least 42" above the base of the stack. (14) Amend Section 409 UPC by adding new subsections (m) and (n) as follows: 409(m) A backwater valve shall be installed in the building drain. It shall be located immediately following the entrance cleanout. No pipe fittings shall be placed between the cleanout and the backwater valve. (n) In buildings, a 3" floor drain shall be installed on the lowest floor. (15) Amend Section 502 UPC by revising subsection (a) and adding a new subsection (c), as follows: 502(a) No vents will be required on a downspout or rain leader trap, a backwater valve, a subsoil catch C 17 9-17-92 basin trap, a three-inch basement floor drain, or a water closet provided its drain branches into the house drain on the sewer side at a distance of five feet or more from the base of the stack and the branch line to the floor drain or water closet is not more than twelve feet in length. (c) In single- and two-family dwellings, no vent will be required on a two-inch basement P trap provided that it drains into a properly vented house drain or branch which is three inches or larger in diameter (except for a water closet branch) on the sewer side at a distance of five feet or more from the base of the stack and the branch to the P trap is not more than eight feet in length. In buildings of one interval, where only a lavatory sink or a urinal empties into the stack, the five-foot distance from the base of the stack does not apply. (16) Amend Section 505 UPC by adding a new subsection (g) to read as follows: (g) No horizontal branch shall exceed 30 feet in length. No vertical stack shall exceed 50 feet in height. Installation exceeding these limits shall be as follows: (A) The bottom portion of a vertical stack over 50 feet shall be cast iron or copper. (B) In horizontal branches exceeding 30 feet, the beginning portion shall be cast iron or copper. (C) Vertical stacks of ABS or PVC plastic shall not have branches of cast iron or copper except in repair and remodel work. (17) Amend Section 507 UPC by adding a new subsection (c) to read as follows: (c) Soil and waste stacks in buildings having more than five branch intervals shall be provided with a relief vent at each fifth interval installed, beginning with the top floor. The size of the relief vent shall be equal to the size of the vent stack to which it connects. The lower end of each relief vent shall connect to the soil or waste stack through a Y below the horizontal branch serving the floor and the upper end shall connect to the vent stack through a Y not less than three (3) feet above the floor levels. (18) Amend Section 608(d) UPC to read as follows: (d) No domestic dishwashing machine shall be directly connected to a drainage system or food waste disposer C 18 9-17-92 without the use of an approved dishwasher air gap fitting on the discharge side of the dishwashing machine, or by looping the discharge line of the dishwasher as high as possible near the flood level of the kitchen sink where the waste disposer is connected. Listed air gap fittings shall be installed with the flood level (FL) marking at or above the flood level of the sink or drainboard, whichever is higher. (19) Amend Section 613 UPC by adding a new subsection (d) as follows: (d) The following wet venting conditions are given as examples of common conditions in residential construction which are allowed under this code, provided the piping sizes are maintained as required by other sections of this code and the wet vented section is vertical. (A) Single bathroom groups. A group of fixtures located on the same floor level may be group vented as limited below: 1. Two fixtures with a combined total of four or less fixture units may be drained into the vent of a three-inch water closet drain. 2. One fixture of two or less units may drain into the vent of a one and one-half inch bathtub drain. 3. Two fixtures of two or less units each may drain into the vent of a two-inch drain serving two or less bathtubs providing that they drain into the vent at the same location. (B) A single bathroom group of fixtures on the top floor may be installed with the drain from a back-vented lavatory serving as a wet vent for a bathtub or shower stall and for the water closet, provided that: 1. Not more than one fixture unit is drained into a one and one-half inch wet vent and not more than four fixture units drain into a two-inch wet vent. 2. The horizontal branch shall be a minimum of two inches in diameter. The horizontal branch may connect to the water closet drain. (C) A common vent may be used for two fixtures set on the same floor level but connecting at different levels in the stack providing that the vertical C 19 9-17-92 drain is one pipe size larger than the upper fixture drain, but not smaller than the lower fixture drain. (D) Where bathrooms or water closets or other fixtures are located on opposite sides of a wall or partition or are adjacent to each other within the prescribed distance, the fixtures may have a common soil or waste pipe and common vent. Water closets having a common soil and vent pipe shall drain into the stack at the same level. (E) Basement water closets or floor drains in one and two family dwellings may be vented by a two-inch drain from a first floor sink or lavatory. (20) Amend Table 7-1 UPC pertaining to Trap Arms to read as follows: Trap Arm Distance Trap to Vent Inches Feet Inches 1-1/4 5 0 1-1/2 6 0 2 8 0 3 12 0 4 and larger 12 0 (21) Amend Section 909 UPC pertaining to Shower Stalls as follows: (a) By adding this sentence to the end of the first paragraph subsection 909(2) UPC: Shower subpans or linings constructed of asphalt impregnated roofing felt shall not be permitted. (b) By deleting the third paragraph of subsection (e)(2) UPC. (22) Amend Section 1004 UPC pertaining to Water Distribution Materials as follows: (a) Water pipe and fittings shall be of brass, copper, cast iron, PVC conforming to AWWA C-900, or other approved materials. CPVC water pipe and tubing may be used for hot and cold water distribution systems within a building. All materials used in the water supply system, except valves and similar devices shall be of a like material, except where otherwise approved by the Administrative Authority. (b) Piping and tubing which has previously been used for any purpose other than for potable water systems shall not be used. C 20 9-17-92 (c) Approved plastic materials may be used in water service piping, provided that where metal water service piping is used for electrical grounding purposes, replacement piping therefor shall be of like materials. Exception: Where a grounding system, acceptable to the Administrative Authority is installed, inspected and approved, metallic pipe may be replaced with non-metallic pipe. (d) Solder shall conform to the requirements of Section 802(d) . (e) This section does not apply to yard sprinkler systems. (23) Amend Section 1007 UPC pertaining to Water Pressure as follows: (a) The first sentence of Section 1007(b) shall read: Where local water pressure is in excess of 110 pounds per square inch (551.2kpa), an approved type pressure regulator preceded by an adequate strainer shall be installed and the pressure reduced to 110 pounds per square inch (551.2kPa) or less. (b) The first sentence of Section 1007(e) shall read: Relief valves located inside a building shall be provided with a drain, not smaller than the relief valve outlet of galvanized steel or hand drawn copper piping and fittings and shall not extend from the valve to the outside of the building. (24) Amend Section 1008 UPC pertaining to Water Service Installation by adding to the end of subsection (a) the following: All water service yard piping shall, whenever feasible, be no less than five feet below the surface of the ground. (25) Delete Section 1009(a) UPC and insert in lieu thereof the following: (a) the size of each potable water supply pipe from the meter or other source of supply to the fixture supply branches, risers, fixtures, connections, outlets or other uses shall be based on the total demand and shall be determined according to the methods and procedures outlined in this section. Water meters shall be sized by the Water Meter Division of the City. Water meter location shall be as provided for in Chapter 28 of the Ames Municipal Code. C 21 9-17-92 Maximum Number of Water Meter Sizing Fixture Units as Determined from Normal Operating Meter Size* UPC Table 10-1 to Flow Range Typical Residential & Size Service Lines in gallons Commercial Applications and Meters per minute (gpm) with Flush Tanks 29 1/4 - 20 5/8" or 5/8" x 3/4" disc type 52 1/2 - 30 3/4" disc type 125 1/2 - 50 1" disc type 275 1 - 80 12" disc type * Meter sizing for other specialty applications (such as flushometer valves) or larger meter sizes shall be determined by the Water Meter Division. (26) Amend Section 1009(h) UPC by adding: An assumed pressure range of 30-45 psi will be used for table 10-2. (27) Add a new Section 1010 to read as follows: Water Service. (A) The water service line shall be type K copper tubing, cast iron, brass or PVC meeting AWWA C-900, 200 psi HDPE C.T.S. meeting ASTM D2737, or other approved materials. Lead or galvanized service lines and lead solder shall not be allowed. Pipe couplings in water service lines shall be by swedge type mechanical joints. Pipe couplings shall not be allowed under concrete or asphalt surfaces, such as streets, driveways, sidewalks, alleys, or floors, except a flare coupling may be allowed provided there is a minimum two-inch cover between the pipe and the concrete/asphalt material. All fittings shall be long-shoulder flare fittings. (B) All water service lines shall be installed at least five feet below finish grade. If the water main and tap cannot be buried below frost depth at any point, the trench shall be lined with 12" thick "Blue Board" insulation or equivalent as approved by the administrative authority. Sand backfill material shall then be placed to a depth of one foot above the top of pipe, then 12" "Blue Board" or equivalent will be installed so that the entire trench width and length in the area needing protection against freezing is insulated and then backfilled. (C) Water service lines of any installation shall be at least 3/4 inch in diameter. Water service lines for any commercial property shall be at least one inch in diameter. Any water C 22 9-17-92 service line 100 feet or more in length shall be at least one inch in diameter. For service lengths of 200 feet or 300 feet, the minimum diameter shall be 14 inches and 12 inches, respectively. It is important to note that these are minimum diameters for service lines. Larger diameters may be required to provide adequate service based on number of fixture units. See Table 10-2. (D) All taps on the main shall be at least 24 inches apart and shall be at least 3/4 inch in size. If more than one tap is made for a service line, the taps will be staggered on the pipe. Maximum tap size for a 4-inch main is 3/4 inch. Maximum tap size for a 6 inch or larger main is one inch. No more than three taps shall be made for a service connected to a 4-inch or larger main. All taps will be made in the top half of the water main but not more than 451 above the horizontal plane. No main shall be tapped nearer than eighteen (18) inches to a joint. Minimum size for any service valve will be 4 inch. No 4 inch by 2 inch tapping valves will be permitted. A 4 inch by 4 inch tapping valve and sleeve is the smallest which may be used. The following table lists appropriate number of taps for different service sites. Service Size Taps 3/4 inch 1 3/4 inch 1 inch 2 3/4 inch or 1 1 inch 1-1/4 inch 3 3/4 inch or 2 1 inch 1-1/2 inch 2 1 inch (Two or more taps shall have 24" minimum spacing and be staggered) All services having two (2) taps or more shall be combined through a brass wye pipe connection. The maximum length of service from the main to the wye shall be four (4) feet. (E) Where a single water service line provides service to a new duplex or is split for any other reason, the service line shall be at least one inch in diameter. Where an existing structure is to be converted to a duplex a 1" equivalent service may be provided by a separate tap. The new service lines shall be divided by a wye at the property line. Existing 1" services may be split inside the building so long as shut offs are available in a common area. Separate curb boxes shall be installed, and separate 3/4 inch service lines shall be run to the individual customer units. (F) In the event a curb box is set in any location where a concrete or asphalt surface is to be placed, a sleeve shall be placed around the cap to allow for expansion and contraction. C 23 9-17-92 (G) In a new subdivision the new water service line shall be installed at the center of the property unless otherwise approved by the administrative authority. (H) Only one service is allowed per structure or development. No extra service line taps into the structure or development from the service line are permitted unless the main service line is a 4 inch minimum size or is of sufficient size to meet the water demands and is approved by the Board of Appeals, except as stated in (E) above. Additional services may be approved by the Board of Appeals. (I) If the proprietors of buildings desire to lay pipes with hydrants and hose couplings to be used only in case of fire, they will be permitted to connect with the street mains, at their own expense, upon application to the City and will be allowed to use the water for fire purposes only, free of charge. (J) Sprinkler systems used for fire protection may be permitted to be attached to the water mains by registered plumbing contractors by direct connection without meters under the direction and supervision of the City. No open connection can be incorporated in the system, and there shall be no valves except a post indicator valve at the entrance to the building which must be sealed open. One and Two family residential sprinkler lines shall be metered through the single meter. The property owner or tenant shall promptly report to the City any seal which has been broken for the closing of the system. A detailed drawing of the sprinkler system shall be filed with the City and free access to the building shall be granted the City for inspection purposes. No charge will be made for water used for fire purposes through a sprinkler system. (K) There shall be a curb cock in every service connection to the main, lateral or extension service supply in streets. It shall be located on the property line or as close as possible thereto and in alleys within one foot of the alley line, except two (2) inch and larger, which shall have a street valve box over the valve at the water main. The curb cock to be used for services from three-fourths (3/4) inch to two (2) inches shall be the style known as Mueller Mark II Oriseal or Ford Ball Valve with 901 curb cock, or equal, provided with T handle and extension rod keyed and locked to curb cock and shall be the same diameter as the pipe served. The curb cock shall be kept in an operative condition at all times. (L) The curb cock shall be covered by a curb box of the Western pattern No. 100, or equal, extending to the curb grade. In cases where the surface of the ground is higher than the C 24 9-17-92 curb grade to the extent that the curb box will not extend sufficiently to be in plain view, then the curb box shall be extended to the ground surface. Whenever a water service is renewed the curb box shall be brought to the curb grade or present natural ground level and moved to the property line. In placing the curb cock in position, care must be exercised to provide against settlement of the curb box, by providing a base of brick, stone or concrete block set on solid earth for support. A support shall be placed across the ditch and wired to the curb box near the top to keep it in a vertical position while filling the ditch. (M) A corporation cock of either a Mueller or Glauber make, or its equivalent, shall be inserted in every tap one inch or less in diameter made in the water main. The connection to the main shall be made by a regulation corporation cock and copper service with a flared joint. All connections to the water main shall be adequately looped to prevent breakage from ditch settlement. All joints to service pipes shall be tested in the presence of and approved by the building official before being covered. (N) Leaking water service connections shall be resolved in accordance with Chapter 28 of the City Code. (28) Amend Section 1101(a) UPC by adding this sentence as follows: More than one sanitary sewer connection to a public sewer may be allowed. (29) Amend Section 1102 UPC by adding subsection (f) as follows: All openings into the sanitary sewer piping within a building must be securely sealed at all times by means of a manufactured plug or seal until the building has been made completely tight against the elements of weather and all backfilling around foundations has been brought to proper grade to insure the drainage of surface water away from the building. (30) Amend Section 1103(a) UPC to read as follows: (a) The building sewer, beginning from two (2) feet ( .6m) from any building or structure, shall be of cast iron, extra strength vitrified clay pipe, or SDR 23.5 polyvinyl chloride pipe (PVC) . PVC pipe shall conform to ASTM D-3034. PVC resin shall meet cell class 12454B per ASTM D 1784. VCP and cast iron shall be installed according to methods specified in ASTMC-12. SDR 23.5 PVC shall be installed according to ASTM D-2321. Embedment material shall meet ASTM C-33 (crushed) gradation 67. C 25 9-17-92 (31) Amend Section 1105 UPC Size of Building Sewers, to read as follows: The size of any building sewer shall be determined on the basis of the total number of fixture units drained by the sewer in accordance with Table 4-3. The minimum diameter for a building sewer shall be four inches. (32) Amend Section 1106 by adding a new subsection (d) as follows: 1106(d) Building sewer depth. Whenever possible the building sewer shall be laid at a depth of not less than nine (9) feet below street grade from the main to the property line. Renewals may be replaced at existing depth, or lower if desired. (33) Amend Sec. 1107 UPC by adding a new subsection (g) as follows Cleanouts shall not be more than 40 feet apart in horizontal drainage lines of 2 inches in diameter or less, more than 90 feet of developed length apart in lines of 3 inches or larger. There shall be an entrance cleanout. A cleanout shall be provided in each vertical waste or soil stack at a point at least 42" above the base of the stack. (34) Add a new section 1120 to read as follow: Sanitary Sewer Service--New Subdivision Construction. (A) This section deals with construction and inspection procedures for installing sanitary sewer service lines where a factory wye or factory wye and riser are already in place. In this situation, the plumbing contractor shall start the stub-in at the existing connection. No additional cut or tap into the sewer main will be permitted. (B) All work will be done in a 'dry ditch'. The generally accepted understanding of a 'dry ditch' is a work area without standing water and without flowing mud. If necessary, the plumber shall over-excavate, furnish and place 1" or smaller concrete stone and provide necessary pumping equipment to maintain dry working conditions. Under no condition shall the plumber discharge surface or groundwater to the sanitary sewer system or do any work in standing water unless on-site authorization is given by the inspector. (C) The sewer service line shall be pipe of 4 inch minimum diameter installed at least five feet below finish grade. If the service line cannot be buried below frost depth at any point, the service line shall be protected in the same manner as specified for water service lines in Sec. 21.501(29)(B), Ames Municipal Code. The property owner also has the option of plumbing to the sewer main. The property owner shall retain full C 26 9-17-92 responsibility for operation and protection of any delivery system to the sewer main. (D) Any service line that is constructed with a greater than 20 percent grade shall be stepped down to the main and anchored as approved by the administrative authority to the undisturbed trench bottom. (E) Cleanouts on service lines shall be provided every 90 feet of developed length and "just upstream" of every change in alignment or grade greater than 451. (F) All joints in the service line, including the first joint at the connection to the main, shall be rootproof and waterproof. Joints shall be fabricated using a preformed compression joint or an equal alternative method approved by the inspector. (G) The service line shall cross the property line at a location such that it will be within three feet horizontally of the curb box after the water service line is laid or as approved by the administrative authority. Stub-ins may then diverge as necessary after entering private property. The termination point of the service line shall be marked at the surface with a durable marker. There shall be an elevation marker on the lot line so curb boxes can be placed at proper height for locating. (H) The entire service line trench from wye or riser to its termination shall remain open and uncovered until inspected and approved for backfill. If the work has been backfilled or covered for any reason including natural causes prior to inspection, the plumber shall be required to uncover it for inspection. (I) After inspection, the entire service line trench shall be backfilled by the plumber in stages as described below. The bedding and the first two feet of protective cover shall be comprised of sand, pea gravel, or other approved material, as directed by the plumbing inspector of the Public Works Department, with such hand work and compaction as required by the inspector to assure the integrity of the sewer service line. After the protective cover is placed and approved, the rest of the backfill within the public right-of-way shall be placed by the plumber under the on-site inspection of the Public Works Department. That backfill shall be mechanically tamped so that all areas in the upper three feet and within five feet of the proposed curb line are compacted to 95 percent of the standard Proctor density and all other areas of the excavation within the right-of-way are compacted to 90 percent of standard Proctor density. The remaining backfill outside the public right-of-way shall also be placed by the plumber. C 27 9-17-92 (J) Final inspection of the connection and the main may be made by TV camera filming of the full-length interior of the sewer main at city expense. (35) Add a new section 1121 to read as follows: Sanitary Sewer Service--Tap into Existing Main. (A) This section deals with construction and inspection procedures for installing sanitary sewer service lines where a factory wye or factory wye and riser do not exist. In this situation, the stub-in will begin with a tap into the sewer main as described below. The tap may be made only in the public right-of-way or in a public easement. (B) Under no condition shall the plumber discharge surface or groundwater to the sanitary sewer system or do any work in standing water unless on-site authorization is given by the inspector. Failure to have or provide adequate dewatering equipment shall not be accepted as justification for waiver of the 'dry ditch' requirement. (C) The tap into the sewer main shall be in the form of a smooth, round hole with a tolerance not to exceed 4 inch diameter larger than the O.D. of the saddle spigot end. No hand cutting or tapping methods will be allowed. Only machine drilling will be permitted with equipment able to retain the coupon cut from the sewer main. This coupon shall be marked with the lot number and given to the inspector at the time of inspection. (D) If the sewer main is cracked or otherwise damaged during drilling, the plumber shall replace the pipe section. Where a pipe section must be replaced, joints must be completed with stainless steel water main type repair clamps with ductile lugs, at least 72 inches in length. For 8 inch main, the repair clamp shall be designed to fit 9.27 to 9.67 inches O.D. pipe. For 4 inch service line, the repair clamp shall be designed to fit 4.45 to 4.73 inches O.D. pipe. No type of flexible coupling will be allowed. The repair of the main shall be inspected by Public Works prior to backfill. (E) The service line connection shall be made with a cast iron saddle tee such as Genoco Sealtite Model #DSBF sewer saddle or approved equal specifically designed for this purpose. The spigot end shall fit smoothly into the wall of the sewer main and shall not protrude more than 4 inch past the inside pipe surface. The saddle flange or collar shall be sealed to the main with a rubber O-ring. The connection shall be secured in place by a stainless steel strap of at least 28 gauge and at least 22 inches width. The saddle for PVC pipe shall be as manufactured for the type of PVC pipe being used. C 28 9-17-92 (F) Building sewer connection. When the building sewer is installed in the connection fitting a root-proof, waterproof joint shall be fabricated by the use of a preformed compression joint or poured joint acceptable to the inspector. The entire connection fitting and building sewer joint assembly shall remain uncovered for inspection and approval before backfill. (G) Factory saddle wyes will not be accepted for making new connections to an existing sewer or for repair work. (H) Final inspection of the connection and the main may be made by TV camera filming of the full-length interior of the sewer main at city expense. (I) All sanitary sewer taps shall be made in the top half of the main but no more than 451 above the horizontal plane. All taps shall be made at least 18 inches apart, at least 24 inches away from any joint. (J) All service lines shall be tapped into the main and not into a manhole except as provided in Subsection (K) below. (K) Any sewer line 6 inch or greater requires a manhole at the public main. The property owner shall retain full responsibility for operation and protection of any delivery system to the sewer main. Any private sewer 8 inches or larger requires a manhole every 300 feet. Approved Materials for Sanitary Services Service Size Material 4 inch Cast Iron, SDR 23.5 PVC, copper 6 inch Extra strength vitrified clay, cast iron, SDR 23.5 PVC, copper 8 inch or larger Truss Pipe Extra strength vitrified clay pipe, cast iron, SDR 35 PVC, copper PVC meeting ASTM F949 (M) That part of the service line trench outside the public right-of-way shall be completely backfilled by the plumber in stages. The bedding and the first two feet of protective cover shall be comprised of approved material, as directed by the Public Works Department. (36) Delete Section 1213(a) UPC and insert in lieu thereof the following: All joints and fittings in a concealed gas piping system shall be welded. Only fittings approved for a welded system shall be C 29 9-17-92 used. Screw type fittings shall not be welded. Screw type fittings may be used in concealed spaces only if accessibility is provided at each fitting location. Access opening shall be of a size that will permit a workable access to fittings requiring repair or replacement. (37) Section 1305 pertaining to Water Heaters is revised by adding these sentences to the end of subsection (c) : The over-temperature safety protection device shall be a combination pressure and temperature relief valve. The valve shall drain indirectly into a floor drain or service sink. (38) Section 1306 pertaining to Oil Burning Heaters is revised by adding these sentences to the end of subsection (b) : The over-temperature safety protection device shall be a combination pressure and temperature relief valve. The valve shall drain indirectly into a plumbing fixture, floor drain, sump pit, or other approved point of discharge. (39) Add a new Chapter 14 to read as follows: Chapter 14. Foundation Drain Service. (A) Discharge Line. The discharge line shall be a pipe with a minimum inside diameter of 12 inches. The discharge line may be polyvinyl chloride (PVC) or polyethylene (PE) pipe. PVC pipe shall be a minimum of Schedule 40 PVC meeting ASTM D-2665 with solvent weld Schedule 80 deep socket fittings. PE pipe shall be a minimum of PE-3408 meeting ASTM D-2239 with joints made with ribbed insert fittings secured by stainless steel clamps. All discharge line piping where fittings are not visible or where there is doubt on the part of the inspector of proper installation, shall be tested for leakage by applying a 30 psi air pressure test for a period of not less than one minute. Any loss of pressure during the test will be cause for rejecting the installed pipe and requiring repair or replacement of defective parts. (B) Depth of Burial. The discharge line shall be buried to a depth of at least 5 feet below the final surface grade. Where that depth of cover cannot be maintained, cold weather protection in the same manner as specified for water service lines in Sec. 21.501(29)(B) , Ames Municipal Code, or by another approved method, shall be required. (C) Check Valve. A check valve shall be provided in the discharge line, whether the discharge line flows by gravity or is pumped. The check valve may be installed in either a vertical or horizontal position. This check valve shall be in addition to any check valve built into the sump pump. C 30 9-17-92 (D) Electrical Service. For a sump pump to be operational, the sump pump shall have a 20-amp circuit and 15-amp outlet. The wire shall be 12-2 w.g. The sump pump shall have a separate circuit. Where the fuse box lacks sufficient capacity or where other electrical deficiencies will not permit routine hookup of electrical service to the sump pump, the homeowner will be so informed. In such cases, additional costs could be incurred by the homeowner to correct the deficiencies. (E) Connection. The discharge line shall be connected to a public storm sewer, collector line, or storm sewer intake if such exists adjacent to the property. The connection to the storm sewer or collector line shall be made by machine tapping and a manufactured fitting, or by an alternate method of an approved tap and saddle on a concrete storm sewer pipe. A tap shall be used on all 6 inch collector lines. A sewer tapping machine shall be used for all tile lines. 1 - The correct saddle to use to connect to a 6"-15" tile line is a Gemco sewer saddle (B.F.O.) . 2 - The correct saddle for a collector line of 6" plastic is a PVC saddle tee secured with stainless steel clamps. 3 - To connect a storm line to a concrete pipe, use a saddle made with a cast iron hub. The pipe will extend from the hub to the face of the pipe. Cement mortar and oakum will be used for a water and root-proof connection to the storm sewer. (F) No Connection Available. If a storm sewer or collector line does not exist in the roadway fronting the property, the discharge line shall be terminated at the back of curb. In the event the storm sewer/collector line is on the opposite side of the pavement, the discharge line shall be extended across the street. Back-of-curb discharges shall be directed downward to the pavement by use of an elbow or other approved arrangement. The City of Ames shall be responsible for the connection to the storm sewer/collector line for those services properly terminated at back-of-curb. (G) Sump Pump. Delivery of the foundation water to an approved point of disposal shall be made using an approved pump system. The sump pump shall be able to deliver 17 gpm against 17 feet of head. (H) Gravity Discharge. In some instances, foundation water may be discharged to an open waterway or other natural drainageway by gravity when approved by the administrative authority. Under no circumstances will a gravity line be approved without backwater control. C 31 9-17-92 (I) Alternative Uses. With prior approval, the property owner may install such piping and valves necessary to allow the foundation water to be used for lawn or garden watering or other such use. However, said diversion facilities shall be in addition to the permanent connection to the storm sewer/collector line. (40) Add a new chapter 15 to read as follows: Chapter 15. Storm Sewer Service 15.1 The storm sewer service line or designed private storm sewer shall be made of cast iron, reinforced concrete pipe (RCP), vitrified clay pipe (VCP), SDR 35 polyvinyl chloride pipe (PVC), PVC truss pipe, or PVC meeting ASTM F949. PVC pipe shall conform to ASTM D-3034. PVC resin shall meet cell class 12454B per ASTM D 1784. 15.2 Installation requirements. Installation shall be completed in accordance with the standard specifications governing pipe installations as established by the Public Works Department. a. RCP, VCP and cast iron shall be installed according to methods specified in ASTM C-12. b. SDR 35 PVC shall be installed according to ASTM D-2321. Embedment material shall meet ASTM C-33 (Crushed) Gradation 67. 15.3 Storm sewer service lines may be connected to the city storm sewer system at intakes or manholes or directly into the city storm sewer pipe. Tapping storm sewer service lines into city storm sewers will be by using approved methods. The connection from the storm sewer service line to the city storm sewer will be made by a clamping saddle or a fitting with a sealant that will be waterproof and rootproof.. The entire connection shall remain uncovered for inspection and approval before backfill. A collar will be installed at the main so that the service line will not protrude into the main. If a storm sewer service line is over half the size of the city storm sewer it will require a manhole at the junction. The manhole shall meet City of Ames Standard Specifications for storm sewer construction. Taps will be installed on the top half of the city storm sewer. Clean outs shall be installed on storm sewer service lines at intervals not to exceed 80 feet of developed length and at locations where the line changes direction more than 45 degrees. If a storm sewer service line is installed with more than 25 percent grade, it will be stepped down with the use of fittings. 15.4 Private storm sewer mains can be connected to the City storm sewer system at intakes or manholes. Connecting into the city storm sewer line with a private storm sewer main requires installation of a manhole or intake at the junction. The C 32 9-17-92 manhole or intake shall meet City of Ames Standard Specifications for storm sewer construction. Manholes or intakes on the private storm sewer line will be installed at intervals not to exceed 300 feet and at all alignment and size changes. The Municipal Engineer shall review and approve all private storm sewer systems designs prior to the issuance of a permit to connect the private storm sewer system to the city storm sewer. 15.5 Permits and applicable fees are required for any storm sewer service lines or private storm sewer systems installed on private property. 15.6 Inspection fees for installations utilizing VCP, RCP or cast iron will be as currently established by City ordinance. Inspection fees for installations using SDR-35 PVC will be as from time to time adopted by city council for full time inspection while the pipe and embedment materials are being placed. Inspection fees for the embedment operation may be waived provided a registered Engineer licensed to do business in Iowa will certify that the pipe embedment has been completed in accordance with the ASTM D-2321 Standards. DIVISION VI. ADDITIONAL REQUIREMENTS Sec. 21.601. PROCEDURE FOR ABATEMENT OF PROHIBITED SEWER CONNECTIONS AND DRAINAGE ARRANGEMENTS. (1) In that surface water runoff, subsoil and footing drainage water is being allowed to enter the sanitary sewer system contrary to Ordinance No. 1011 enacted December 19, 1961 and other ordinanc- es of the city to the public detriment from resulting sewer back ups and overloading of the sewage treatment plant, any connection or arrangement found to exist whereby surface, subsoil or footing drainage water is discharged or diverted into the sanitary sewer system is deemed to be, and hereby declared as, a public nui- sance. (2) Whenever such connection or arrangement is found to exist in violation of the ordinances of this city, whereby surface water runoff, subsoil or footing drainage is discharged or diverted into the sanitary sewer system, the city council may, after notice to the owner or person in possession and control of the premises and opportunity for a hearing, cause such to be abated by ordering a connection to a public drainage system, storm sewer system, natural watercourse or such other arrangement as the council shall find necessary, adequate or appropriate, given the particulars and circumstances of each case. (3) If the person or persons so ordered fail to comply with the coun- cil's order within the time prescribed when the order is made, the C 33 9-17-92 council may cause the ordered work to be done, an accounting of the cost of such work made and reported, and by resolution of the council certify to the county auditor for collection in the same manner as property taxes. (4) In addition to, or as an alternative to the foregoing, such prescribed connections may be charged as a municipal infraction and relief sought as appropriate under that procedure as by law provided. ARTICLE VII. PENALTY Sec. 21.701. PENALTY. Any person, corporation or other legal entity who violates or resists the enforcement of any of the provisions of this ordinance commits a municipal infraction punishable by a civil penalty of thirty dollars ($30) for the initial offense, one hundred dollars ($100) for the second offense, and two hundred dollars ($200) for each repeat offense. Each day that a municipal infraction occurs constitutes a separate offense. Any person, corporation or other legal entity who violates this ordinance after having previously been found guilty of violating the same ordinance provision at the same location or at a different location shall be considered to have committed a repeat offense. Seeking a civil penalty as authorized in this section does not preclude the city from seeking alternative relief, including an order for abatement or injunctive relief. Section Two. All ordinances or parts of ordinances in conflict herewith are hereby repealed to the extent of such conflict, if any. Section Three. This ordinance shall be in full force and effect April 1, 1993, from and after its passage and publication as required by law. Passed this 24th day of September 92 ,_--- Jill Ripper ,er, Acting City Clerk Larry Curtis, yor 02 C 34 9-17-92